UPS参照表
UPS输出功率与放电时间(分钟)的关系:
1. 环境温度 (25oC)
2. 电池组的标称电压48V和96V
3. 最低电县.8V/单格
4. 未考虑功率补偿因素
型号
|
Volts
|
300VA
|
500VA
|
1KVA
|
2KVA
|
3KVA
|
5KVA
|
7.5KVA
|
10KVA
|
15KVA
|
20KVA
|
SJ6V4.5Ah
|
48V
|
17
|
7
|
|
|
|
|
|
|
|
|
96V
|
46
|
23
|
7
|
|
|
|
|
|
|
|
SJ6V5Ah
|
48V
|
28
|
14
|
|
|
|
|
|
|
|
|
96V
|
62
|
35
|
1.4
|
|
|
|
|
|
|
|
SJ6V7.2Ah
|
48V
|
39
|
19
|
5
|
|
|
|
|
|
|
|
96V
|
90
|
49
|
19
|
5
|
|
|
|
|
|
|
SJ6V10Ah
|
48V
|
62
|
31
|
8.5
|
|
|
|
|
|
|
|
96V
|
140
|
78
|
31
|
8.5
|
|
|
|
|
|
|
SJ6V12Ah
|
48V
|
72
|
38
|
15
|
|
|
|
|
|
|
|
96V
|
170
|
92
|
38
|
15
|
6.6
|
|
|
|
|
|
SJ12V4.2Ah
|
48V
|
17
|
7
|
|
|
|
|
|
|
|
|
96V
|
46
|
23
|
7
|
|
|
|
|
|
|
|
SJ12V5Ah
|
48V
|
28
|
14
|
|
|
|
|
|
|
|
|
96V
|
62
|
35
|
1.4
|
|
|
|
|
|
|
|
SJ12V7Ah
|
48V
|
39
|
19
|
5
|
|
|
|
|
|
|
|
96V
|
90
|
49
|
19
|
5
|
|
|
|
|
|
|
SJ12V18Ah
|
48V
|
|
61
|
22
|
5.6
|
|
|
|
|
|
|
96V
|
|
|
61
|
22
|
10
|
|
|
|
|
|
SJ12V24Ah
|
48V
|
|
|
39
|
12
|
5
|
|
|
|
|
|
96V
|
|
|
100
|
39
|
20
|
7.5
|
|
|
|
|
SM12V33Ah
|
48V
|
|
|
50
|
22
|
13
|
6
|
|
|
|
|
96V
|
|
|
120
|
50
|
30
|
15
|
11
|
|
|
|
SM12V38Ah
|
48V
|
|
|
75
|
26
|
13
|
4
|
|
|
|
|
96V
|
|
|
|
75
|
40
|
18
|
8.6
|
|
|
|
SM12V65Ah
|
48V
|
|
|
|
50
|
28
|
12
|
5
|
|
|
|
96V
|
|
|
|
|
79
|
35
|
19
|
|
|
|
SM12V100Ah
|
48V
|
|
|
|
|
58
|
25
|
11
|
5
|
|
|
96V
|
|
|
|
|
120
|
68
|
40
|
25
|
11
|
|
SM12V120Ah
|
48V
|
|
|
|
|
70
|
30
|
15
|
8
|
|
|
96V
|
|
|
|
|
|
82
|
50
|
29
|
15
|
8
|
SM12V150Ah
|
48V
|
|
|
|
|
|
50
|
22
|
13
|
7
|
|
96V
|
|
|
|
|
|
100
|
75
|
50
|
22
|
10
|
SM12V200Ah
|
48V
|
|
|
|
|
|
|
45
|
20
|
12
|
6
|
96V
|
|
|
|
|
|
|
110
|
80
|
45
|
20
|
|